Water Blocked P3 or P3/P10 RFOU/TFOU 6/10KV
Applications
-
These cables are partially water blocked, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.
标准
-
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004 VG 95218 part 29
Construction
-
l Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.
l Conductor Screen: Semi conducting material.
l Insulation: Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
l Insulation Screen: Semi conducting material and tinned copper wire braid.
l Filler: Water blocking fillers, if required.
l Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
l Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
l Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
l Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P3), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P3/P10), coloured red.
l Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
Electrical Characteristics
-
Nominal Cross Section Area mm² 16 25 35 50 70 95 120 Nominal Conductor Diameter mm 5.2 6.5 7.4 8.7 10.3 12.2 13.8 Maximum DC Resistant@20℃ Ω/km 1.16 0.734 0.529 0.391 0.27 0.195 0.154 Continuous Current Rating@45℃1 Core A 96 127 157 196 242 293 339 Continuous Current Rating@45℃3 Core A 67 89 110 137 169 205 237 Short Circuit Current 1s A 2290 3580 5010 7150 10020 13590 17170 Operating Voltage KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10
-
Nominal Cross Section Area mm² 150 185 240 300 400 500 630 Nominal Conductor Diameter mm 15.1 17.0 19.6 21.9 24.5 27.5 32.3 Maximum DC Resistant@20℃ Ω/km 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286 Continuous Current Rating@45℃1 Core A 389 444 522 601 690 780 890 Continuous Current Rating@45℃3 Core A 272 311 365 421 483 546 623 Short Circuit Current 1s A 21460 26470 34340 42930 57230 71540 90140 Operating Voltage KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10
Ambient Temperature Correction Factors
-
Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80 Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Mechanical and Thermal Properties
- Bending Radius :15×OD (during installation); 9×OD (fixed installed).
- Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight
Construction No. of cores×Cross section(mm²) | Nominal Insulation Thickness mm | Nominal Bedding Thickness mm | Nominal Inner Sheath Thickness mm | Nominal Outer Sheath Thickness mm | ||
Nominal Overall Diameter mm |
Nominal Weight kg/km |
|||||
1×16 | 3.4 | 1.5 | 1.1 | 1 | 26.0±2 | 945 |
1×25 | 3.4 | 1.5 | 1.2 | 1.2 | 28.4±2 | 1197 |
1×35 | 3.4 | 1.6 | 1.2 | 1.2 | 29.3±2 | 1328 |
1×50 | 3.4 | 1.6 | 1.2 | 1.2 | 30.7±2 | 1533 |
1×70 | 3.4 | 1.7 | 1.3 | 1.2 | 32.4±2 | 1796 |
1×95 | 3.4 | 1.8 | 1.3 | 1.4 | 34.8±2 | 2163 |
1×120 | 3.4 | 1.8 | 1.4 | 1.4 | 36.6±2 | 2499 |
1×150 | 3.4 | 1.9 | 1.4 | 1.4 | 38.1±2 | 2835 |
1×185 | 3.4 | 2 | 1.5 | 1.4 | 40.6±2 | 3386 |
1×240 | 3.4 | 2.1 | 1.6 | 1.6 | 44.2±2 | 4190 |
1×300 | 3.4 | 2.2 | 1.6 | 1.6 | 46.9±2 | 4998 |
1×400 | 3.4 | 2.3 | 1.7 | 1.6 | 48.7±2 | 6195 |
1×500 | 3.4 | 2.4 | 1.8 | 1.6 | 52.7±2 | 7718 |
1×630 | 3.4 | 2.6 | 1.9 | 1.6 | 57.7±2 | 9188 |
3×16 | 3.4 | 2.3 | 1.7 | 1 | 48.0±2 | 3465 |
3×25 | 3.4 | 2.4 | 1.8 | 1.2 | 52.5±2 | 4100 |
3×35 | 3.4 | 2.5 | 1.8 | 1.2 | 54.6±2 | 4578 |
3×50 | 3.4 | 2.6 | 1.9 | 1.2 | 57.5±2 | 5444 |
3×70 | 3.4 | 2.7 | 2 | 1.2 | 61.3±2 | 6431 |
3×95 | 3.4 | 2.9 | 2.1 | 1.4 | 66.3±2 | 7875 |
3×120 | 3.4 | 3 | 2.2 | 1.4 | 70.4±2 | 9214 |
3×150 | 3.4 | 3.2 | 2.3 | 1.4 | 74.1±2 | 10747 |
3×185 | 3.4 | 3.4 | 2.4 | 1.4 | 76.8±2 | 11865 |
3×240 | 3.4 | 3.6 | 2.6 | 1.6 | 82.7±2 | 13965 |
3×300 | 3.4 | 3.8 | 2.7 | 1.6 | 88.2±2 | 17115 |